Inf6, Function, Command/response (for normal operation) – Yokogawa PR300 Power and Energy Meter User Manual
Page 74: Example
<Toc> <Ind>
<4. PC Link Communication Protocol>
4-13
IM 77C01E01-10E
INF6
Reads the model, suffix codes, and version information
●
Function
This function code reads the model, suffix codes, and version number of the PR300.
•
For the format of response in the event of failure, see subsection 4.1.2.
●
Command/Response (for normal operation)
Response (continued)
Number
of Bytes
Command
element
1
STX
2
Station
number
(ST-NO)
3
INF
2
6
2
01
1
1
Checksum
1
ETX
1
CR
Number
of Bytes
Response
element
1
STX
2
Station
number
(ST-NO)
2
01
2
OK
4
Version and
revision
numbers
(Note 2)
4
Start
register
specified for
readout
refreshing*
1
4
Number of
registers
specified for
readout
refreshing*
22
12
Model code:
PR300
✩★■■■■■
(Note 1)
4
Number of
registers
specified for
write
refreshing*
0
Start
register
specified for
write
refreshing*
1
4
2
Checksum
1
ETX
1
CR
0
The * mark indicates fields the FA-M3’s UT link module refers to.
Note 1: Model and suffix code information
PR300–
✩★ᮀᮀᮀ
–
ᮀᮀ
<Model>–<Suffix code>
✩
: Returns the currently selected phase and wire system
1: Single-phase two-wire system
2: Single-phase three-wire system
3: Three-phase three-wire system
4: Three-phase four-wire system
5: Three-phase four-wire system (2.5 element)
★
: Returns the currently selected input range
1: 150 V/1 A
2: 150 V/5 A
3: 300 V/1 A
4: 300 V/5 A
5: 600 V/1 A
6: 600 V/5 A
(*
★
and
✩
are decided by the settings of the phase and wire system and the input range.)
ᮀ
: Returns the suffix code as is
Example:
Suffix code: PR300-32333-6A-0;
Selected phase and wire system:
Single-phase three-wire system; and
Selected input range: 300 V/5 A; then
PR300243336A
Note 2: Version number and revision number
<Revision number>
<Version number>
Example: 0102
(version number + revision number)
Not returned
●
Example
To read the model, suffix code etc. of PR300 at station number 01:
[Command]
[STX]01010INF605[ETX][CR]
In response to this command, the following values will be returned:
Phase and wire system: Single-phase three-wire system
Rated input voltage/current: 300 V/5 A AC
I/O function: Analog output and pulse output
Communication function: Ethernet
Optional measuring function: Demand measurement
Phase indication format: R, S, and T indications
[Response]
[STX]0101OKPR300243336R01020001002200010000E1[ETX][CR]