<3. Procedures for Setting PR300 Functions>

3-15

IM 77C01E01-10E

3.4.6

Demand Alarm Release Function

[Procedure]

(1)

Write a demand alarm release function value to the D register in the table below. The
data type is integer.

(2)

After writing that value, write 1 to the demand measurement writing status register,
D0226.

D Register

D0225

D0226

Reference No.

40225

40226

H No.

00E0

00E1

Description

Demand alarm release
function

Demand measurement writing
status (D0218 to D0225 are
validated)

Effective Range

0: Automatic

release

1: Manual release

If other than 1: Invalid
If 1: Writing is executed

Initial value of demand alarm release function: 0 (automatic release)

[Example]

To set the demand alarm release function to 0 (automatic release):

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX]01010WRW02D0225,0000,D0226,0001[ETX][CR]

[Response]

[STX]0101OK[ETX][CR]

NOTE

A demand alarm release function value can be set for the PR300 with demand mea-
suring function.

When the demand alarm release function is used by digital input, releasing via com-
munication is not possible.