3 lead reactive energy, Lead reactive energy -28 – Yokogawa PR300 Power and Energy Meter User Manual
Page 51
3-28
<Toc> <Ind>
<3. Procedures for Setting PR300 Functions>
IM 77C01E01-10E
3.6.3
LEAD Reactive Energy
[Procedure]
(1)
Write a LEAD reactive energy value to the two D registers in the table below. The data
type is integer.
(2)
After writing that value, write 1 to the writing status register, D0381.
D Register
D0377
Reference No.
40377
H No.
0178
Description
LEAD reactive energy-setpoint
(lower 2 bytes)
Effective Range
Refer to the "NOTE" below.
D0378
40378
0179
LEAD reactive energy-setpoint
(upper 2 bytes)
D0381
40381
017C
Reactive energy writing status
(D0377 to D0380 are validated)
If other than 1: Invalid
If 1: Writing is executed
[Example]
To set the LEAD reactive energy value to 10,000,000 kVarh:
For station number 01, use PC link communication (without checksum) and the random
write command as shown below:
If 10,000,000 is converted into a hexadecimal value, the value is 0098 9680. Then the
order of the upper two bytes and the lower two bytes is reversed
⇒
9680 0098.
[Command]
[STX] 01010WRW03D0377, 9680, D0378, 0098, D0381, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
NOTE
The set LEAD reactive energy value range of the PR300 changes depending on the values
of the VT and CT ratios. The table below shows the set value range.
[Secondary Rated Power]
ϫ
[VT Ratio]
ϫ
[CT Ratio]
Less than 100 kW
100 kW to less than 1 MW
1 MW to less than 10 MW
10 MW or greater
Possible Set Value Range
0 to 99999 kvarh
0 to 999999 kvarh
0 to 9999999 kvarh
0 to 99999999 kvarh
NOTE
The secondary rated power of the PR300 changes depending on its model and suffix codes.