14

Implemented CIP™ objects

14.1

General CIP objects

125

Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Instance attributes for input data of the scanner

The assembly input objects (adapter to scanner) are mapped in the adapter memory starting with

byte 0.
The input objects are transmitted in a "modeless" manner, i.e. a 4-byte header is not included in the

transfer.
So the start address in the assembly memory map is the actual start of the first assembly data

element.
Please observe the actual assembly lengths when mapping the input objects to the controller

memory.
The

Lenze Class (103 / 0x67)

( 141)

provides the image of the scanner input data.

Instance attribute "Data" (attribute 3)

Supported service codes

Attribute

ID

Service

Name

Data type

Value

3

Get / Set Data

Array of BYTE Max. 64 bytes to the scanner

4

Get

Size

UINT

Number of bytes in attribute 3 (Data)

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

110

(0x6E)

0

Custom Output

...

...

31

Custom Output

111

(0x6F)

0

Custom Input

...

...

31

Custom Input

Service code

[hex]

Name

Description

0x0E

Get_Attribute_Single

Outputs the value of a certain attribute.

0x10

Set_Attribute_Single

Changes the value of a certain attribute.