8i/o data transfer (implicit messages) – Lenze E94AYCEO User Manual

Page 60

Advertising
background image

Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17

60

8

I/O data transfer (implicit messages)

8.3

I/O configuration with »RSLogix 5000« version 19 or lower

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5. Go to the "New Module" dialog window and define the properties of the newly added

device .
The terms "input" and "output" refer to the point of view of the scanner:

• Assembly input objects (input) are sent from the adapter to the scanner.
• Assembly output objects (output) are sent from the scanner to the adapter.

Example settings

6. Complete the settings with OK.

Settings

Description

Name

Device name or drive type, usually referring to the process (in the example

"My_E94AYCEO")

Comm Format

Data format for the assembly object instances ("connection parameters" area)

IP Address

IP address of the drive

• The IP address must be in the same subnetwork like the controller. (Depending on

the subnet mask; in general, the first 3 octets of the IP address must be identical.)

• DNS is not supported; the host name merely describes the device.

Input

Assembly object instance for input objects

• Max. 32 input data words (64 bytes, 16 bits/word)

• The number of input data must correspond to the length of the mapped ports in

the transmit PDO (PDO_TX0), otherwise the adapter will reject the connection

with the error message "Invalid Target to Originator Size" (0x0128).

Output

Assembly object instance for output objects

• Max. 32 output data words (64 bytes, 16 bits/word)

• The number of output data must correspond to the length of the mapped ports

in the receive PDO (PDO_RX0), otherwise the adapter will reject the connection

with the error message "Invalid Originator to Target Size" (0x0127).

Configuration

Select the assembly instance "1" and the size "0" for the configuration. These values

are required!

Advertising