C13842 | supervisor ip address, C13843 | supervisor mac id, C13846 | address conflict detection – Lenze E94AYCEO User Manual

Page 96: C13850 | all words to scanner, 13 parameter reference

Advertising
background image

Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17

96

13

Parameter reference

13.2

Parameters of the communication module for slot MXI1

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13842

C13843

C13846

C13850

Parameter | Name:

C13842 | Supervisor IP Address

Data type: UNSIGNED_8

10733 = 0x29ED

Display of the supervisor IP address

(Instance attribute 10 (Supervisor IP Address) in the

Device Level Ring (DLR) Object (71 / 0x47) ( 128)

)

Display range

(min. value | unit | max. value)

0

255

Subcodes

Info

C13842/1

Supervisor IP address (most significant byte)

C13842/2

Supervisor IP Address

C13842/3

Supervisor IP Address

C13842/4

Supervisor IP address (least significant byte)

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13843 | Supervisor MAC ID

Data type: OCTET_STRING

Index: 10732 = 0x29EC

Display of the supervisor MAC ID

(Instance attribute 10 (Supervisor MAC Address) in the

Device Level Ring (DLR) Object (71 / 0x47) ( 128)

)

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13846 | Address Conflict Detection

Data type: UNSIGNED_8

Index: 10729 = 0x29E9

Activation of the address conflict detection (ACD)

(Instance attribute 10 (Selectcd) in the

TCP/IP Interface Object (245 / 0xF5) ( 132)

)

Changing this value requires a reset of the device ("power off/on" or "type 0 reset").
Selection list

(Lenze setting printed in bold)

0 Deactivated
1 Enable

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13850 | All words to scanner

Data type: INTEGER_16

Index: 10725 = 0x29E5

Display of the I/O data words transferred from the communication module (adapter) to the scanner.

In the subcodes, all I/O data words transferred to the scanner are displayed. However, only the configured I/O data

words are valid.
Display range

(min. value | unit | max. value)

-32768

32767

Subcodes

Info

C13850/1
...
C13850/32

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT