Commissioning

6.4

Setting the IP configuration

40

Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 9.0 EN · 12/2013 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.4.2

Setting via codes in the »Engineer«

In the »Engineer« under the Settings tab you can set the IP parameters manually via code.

The IP parameters are written to codes

C13000

/

C14000

(IP address),

C13001

/

C14001

(subnet

mask) and

C13002

/

C14002

(gateway address).

How to activate changed settings in the »Engineer«:

1. Execute the device command C00002 = "11: Save start parameters".
2. Carry out a "Reset node" of the node, or switch the voltage supply of the communication

module off and then on again

Note!

• The IP address must only be allocated manually in the »Engineer« if the PROFINET

network is not operated on the IO controller yet (IP address has not been allocated by

the IO controller yet).

• While setting the IP parameters in the »Engineer«, PROFINET communication with the

IO controller must not take place at the same time.

• The currently used parameter values are shown in codes

C13010

/

C14010

(IP

address),

C13011

/

C14011

(subnet mask), and

C13012

/

C14012

(gateway address).