2 acyclic data transmission process, Acyclic data transmission process, 9parameter data transfer – Lenze E94AYCER User Manual

Page 57

Advertising
background image

Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 9.0 EN · 12/2013 · TD17

57

9

Parameter data transfer

9.1

The acyclic channel (PROFIdrive profile)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.1.2

Acyclic data transmission process

[9-2]

Data communication via the acyclic channel

• A "Write.req" is used to transmit the data set (DB47) in the form of a parameter request to the

IO device.

• "Write.res" confirms the receipt of the message by the IO controller.
• The IO controller requests the response of the IO device with "Read.req".
• The IO device responds with a "Read.res (-)" if processing is not yet completed.
• After parameter processing, the parameter request is completed by transmitting the parameter

response in the form of a "Read.res (+)" to the IO controller.

E94YCER011

Write.res

with data (parameter request)

with data (parameter response)

without data

without data

without data

without data

Read.req

Read.res (-)

Read.req

Read.res (+)

Parameter response

Parameter request

Parameter request

Parameter
processing

Parameter response

IO controller

IO device

Write.req (DB47)

Advertising