Electrical installation
Wiring with a host (master)

5

l

20

EDS82ZAFIC EN 2.0

5.2.2

Wiring with a host (master)

GG

+

E82ZAFICxxx

GG

+

E82ZAFICxxx

GG

+

E82ZAFICxxx

400 m

400 m

1

2

2

2

3

3

3

E82ZAFI008

No.

Element

Description

1

Host

E.g. PC or PLC with INTERBUS master interface module

2

Bus cable

Connects the INTERBUS master interface module to the function modules.

3

INTERBUS slave

Applicable standard device (

^ 10) with function module.

l

Set DIP switch S1 (

^ 29):

– Setting for the last node = OFF
– Setting for all other nodes = ON

Specification of the transmission cable

General characteristics

Cable type

Sold by the meter,
(e.g. PHOENIX CONTACT: IBS RBC Meter−T, Order No. 28 06 28 6)

Number of conductors

3 × 2, twisted pairs, with shared shield

Conductor cross−section

> 0.2 mm

2

DC cable resistance

< 96

W/km

Impedance (characteristic)

l

120

W ± 20 % (f = 64 kHz)

l

100

W ±15 W (f > 1 MHz)

Capacitance per unit length

< 60 nF/km (f = 800 Hz)