Publication GMSI10-UM010C-EN-P - May 2010

28 Installing the XM-120 Eccentricity Module

Figure 2.16 Buffered Output Connections

IMPORTANT

Applies only to XM-120 module revision D01 (and
later).

The voltage operating range of the buffered outputs must
be configured to coincide with the corresponding
transducer bias range. This operating range is configured by
placing a jumper from terminal 5 (channel 1) and terminal
22 (channel 2) to either terminal 6 (Positive Buffer Bias) or
terminal 21 (Buffer -), depending on the transducer. See
Table 2.2. Note the buffered output operating range is
configured independently per channel.

Table 2.2 Configuring Buffered Output Input Range

Transducer

Input Range

Channel

Connect Terminal

To Terminal

Negative Bias

-24 to +9 V

1

5

21

2

22

21

Positive Bias

-5 to +24 V

1

5

6

2

22

6

Non-Bias

-5 to +9 V

1

----

----

2

----

----