Rockwell Automation 1440-VST02-01RA XM-120 Eccentricity Module User Manual
Page 99
Publication GMSI10-UM010C-EN-P - May 2010
DeviceNet Objects 91
1
The Poll Connection Produced Connection Path and Size parameters cannot be set while the Poll connection is
already established with a master/scanner. Attempting to do so will result in an “Object State Conflict” error
(error code 0xC). These Parameter instances are a little more flexible than the actual Connection Object
attributes because they can be set while the connection is in the NON=EXISTENT state (before the master/
scanner allocated the connection).
5
No
Eccentricity 1 Update Rate
USINT
1-255 seconds
60
6
No
Eccentricity 2 Update Rate
USINT
1-255 seconds
60
7
No
Relay 1 Alarm Identifier A
USINT
0 = Alarm 1
1 = Alarm 2
0
8
No
Relay 2 Alarm Identifier A
USINT
0 = Alarm 1
1 = Alarm 2
0
9
No
Relay 3 Alarm Identifier A
USINT
0 = Alarm 1
1 = Alarm 2
0
10
No
Relay 4 Alarm Identifier A
USINT
0 = Alarm 1
1 = Alarm 2
0
11
No
Relay 5 Alarm Identifier A
USINT
0 = Alarm 1
1 = Alarm 2
0
12
No
Relay 1 Alarm Identifier B
USINT
0 = Alarm 1
1 = Alarm 2
0
13
No
Relay 2 Alarm Identifier B
USINT
0 = Alarm 1
1 = Alarm 2
0
14
No
Relay 3 Alarm Identifier B
USINT
0 = Alarm 1
1 = Alarm 2
0
15
No
Relay 4 Alarm Identifier B
USINT
0 = Alarm 1
1 = Alarm 2
0
16
No
Relay 5 Alarm Identifier B
USINT
0 = Alarm 1
1 = Alarm 2
0
17
No
Poll Connection Produced
Connection Path
1
USINT
101-104 (Assembly Object
instance number)
101
18
No
Poll Connection Produced
Connection Size
1
UINT
4 - 124
36
Table C.25 Parameter Object Instances
Instance
Read
Only
Name
Data Type
Valid Values
Default Value