Instance attributes, Services, Instance attributes services – Rockwell Automation 1440-VST02-01RA XM-120 Eccentricity Module User Manual

Page 97

Advertising
background image

Publication GMSI10-UM010C-EN-P - May 2010

DeviceNet Objects 89

Instance Attributes

Services

1

Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.

Table C.22 Analog Input Point Object Class Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

3

Get

Value

REAL

Measurement value

The measured vale in units
specified by the Data Units
attribute.

4

Get

Status

BOOL

Indicates if a fault or
alarm has occurred.

0 = Operating without alarms or
faults
1 = Alarm or fault condition
exists. The Value attribute may
not represent the actual field
value.

8

Get

Value Data Type USINT

Determines the data type
of the Value.

1 = REAL

147

Get

Data Units

ENGUNIT

The units context of the
Value attribute.

See DeviceNet Specification
Volume 1 Appendix K.

Valid values for eccentricity:
mils = 0800 hex
µm = 2204 hex

Fixed for Min/Max Gap
Volt = 2D00 hex

Table C.23 Analog Input Point Object Services

Service
Code

Class/Instance Usage

Name

Description

0E

h

Class/Instance

Get_Attribute_Single

Returns the contents of the
specified attribute.

10

h

Instance

Set_Attribute_Single

Sets the contents of the
specified attribute.

1