Instance attributes, Services, Instance attributes services – Rockwell Automation 1440-VST02-01RA XM-120 Eccentricity Module User Manual
Page 97
Publication GMSI10-UM010C-EN-P - May 2010
DeviceNet Objects 89
Instance Attributes
Services
1
Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
Table C.22 Analog Input Point Object Class Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics
3
Get
Value
REAL
Measurement value
The measured vale in units
specified by the Data Units
attribute.
4
Get
Status
BOOL
Indicates if a fault or
alarm has occurred.
0 = Operating without alarms or
faults
1 = Alarm or fault condition
exists. The Value attribute may
not represent the actual field
value.
8
Get
Value Data Type USINT
Determines the data type
of the Value.
1 = REAL
147
Get
Data Units
ENGUNIT
The units context of the
Value attribute.
See DeviceNet Specification
Volume 1 Appendix K.
Valid values for eccentricity:
mils = 0800 hex
µm = 2204 hex
Fixed for Min/Max Gap
Volt = 2D00 hex
Table C.23 Analog Input Point Object Services
Service
Code
Class/Instance Usage
Name
Description
0E
h
Class/Instance
Get_Attribute_Single
Returns the contents of the
specified attribute.
10
h
Instance
Set_Attribute_Single
Sets the contents of the
specified attribute.
1