Commissioning
Operating Manual PNOZ s30
1001715-EN-13
52
Level
Indication
on the display
Description
Settings
4
(F1 ... F9) (P0 …
P15)
Function
Position (1 … 4)
Select position monitoring 1 ... 4
4
(F1 ... F9) (P0 …
P15)
(Direct. Left, Direct.
Right)
Select left-hand or right-hand di-
rection monitoring
1
Assign
Outputs
Assign functions to outputs
2
Output
(Rel.1... Out 4)
Default:
Off
Each output can be assigned a
switch function (F1 ... F9) or a
range (F2-F3, F4-F5, F6-F7, F8-
F9). Each output can also be used
as an error output (error) or be
switched off (off).
When used as an error output, the
following applies:
Error: Output off
No error: Output on
For ranges, the following applies:
The lower range limit is the switch
function with the lower number
(e.g. F2),
The upper range limit is the switch
function with the higher number
(e.g. F3).
Outputs:
Rel.1: Relay output 1
Rel.2: Relay output 2
Ext.3: External output 1
Ext.4: External output 2
Out 1 … Out 4: Semiconductor
outputs 1 ... 4
- Off
- F1 ... F9
- F2-F3
- F4-F5
- F6-F7
- F8-F9
- Error
1
Start mode
Select start behaviour
2
Start mode
(Rel.1... Out 4)
Default:
Monitored /
Select start mode for each output
separately
Automatic: Automatic start
Monitored /: Monitored start with
rising edge at S34
Monitored \: Monitored start with
falling edge at S34
- Automatic
- Monitored /
- Monitored \