For all units with Economizers:

1. 1.The outdoor temperature is below the Econo Cool Hi

Temp Limit (ConfigurationECONEH.LO) and above

the

Econo

Cool

Lo

Temp

Limit

(ConfigurationECONEL.LO).

For units with Enthalpy Control

2. 1.The outdoor enthalpy is low and the outdoor temperature

is

below

the

Econo

Cool

Hi

Temp

Limit

(ConfigurationECONEH.LO) and above the Econo

Cool Lo Temp Limit (ConfigurationECONEL.LO).

If the conditions above are true and the economizer is available for
cooling the economizer outside air and return air dampers will

modulate to allow proportions of outside air and return air to mix
and produce a temperature equal to the Cool Supply Air Set Point

(SetpointSASP).

If reset is applied to the Supply Air

Temperature Set Point (SetpointSASP) the dampers will control

to the Supply Air Control Point (Run StatusCOOLSA.CP).
If the conditions above are true but the economizer dampers are not
able to satisfy the Cool Supply Air Set Point (SetpointSASP)

with Reset (if applied), the compressor will turn on and modulate

to provide additional cooling to satisfy the Cool Supply Air Set
Point (SetpointSASP) with Reset if applied.
If the conditions above are not true, the economizer will move to a
user

Configurable

Econ

Min

at

Max

Fan

Speed

(ConfigurationECONMP.MX)

where

the

minimum

economizer damper position is based on the Supply Fan Maximum
Speed (ConfigurationUNITFS.MX).

This is done to

maintain a constant airflow through the economizer by opening the
dampers more as the indoor fan speed is reduced or closing the

dampers more as the indoor fan speed increases.
The shape of the Economizer Minimum Position vs. Fan Speed

curve is determined by the configuration parameters: Econ Min at

25% Fan speed (ConfigurationECONMP.25), Econ Min at

50% Fan speed (ConfigurationECONMP.50), Econ Min at

75% Fan speed (ConfigurationECONMP.75) and Econ Min

at Max Fan speed (ConfigurationECONMP.MX).
The

Econ

Min

at

25%

Fan

speed

(ConfigurationECONMP.25), Econ Min at 50% Fan speed

(ConfigurationECONMP.50) and Econ Min at 75% Fan

speed (ConfigurationECONMP.75) damper positions are

calculated based on the Econ Min at Max Fan Speed

(ConfigurationECONMP.MX) and Supply Fan Maximum

Speed (ConfigurationUNITFS.MX).
The

Econ

Min

at

25%

Fan

speed

(ConfigurationECONMP.25), Econ Min at 50% Fan speed

(ConfigurationECONMP.50) and Econ Min at 75% Fan

speed (ConfigurationECONMP.75) damper position are user

configurable and can be determined by setting the fan speed at 25,

50 and 75% and determining the damper position required to

maintain

the

Econ

Min

at

Max

Fan

Speed

(ConfigurationECONMP.MX) Outside air CFM through the

economizer outside air dampers.

The default calculations

programmed into the PD controls is based on a side shot

economizer at 400 CFM/TON Supply Air flow with negative 0.25

in H

2

O pressure in the return duct.

Econ Min at Max fan Speed (ConfigurationUNITFS.MN) is

set by user based on minimum required outside air ventilation
CFM required for the application. This procedure would be the

same as if this were a CV unit with the unit running at the design

point CFM. This determines the minimum position amount of
outside air CFM required when the fan is running at maximum

speed.
Configure

the

Indoor

Fan

Max

Speed

CFM

(ConfigurationECONIDF.C) either to the supply CFM

determined from the fan performance tables or air balance reports.

If using fan performance tables make corrections for all installed

accessory pressure loss and use measured RPM, power and static

pressure readings to determine the actual Indoor Fan Max Speed
CFM (ConfigurationECONIDF.C).

MINIMUM

IAQ

DAMPER

POSITION

(AQ. MN)

ECON MIN

AT MAX

FANSPEED

POSITION

(MINP_MAX)

INCREASING VENTILATION

VENTILATION FOR PEOPLE

VENTILATION FOR SOURCES

100

700

INSIDE/OUTSIDE CO

2

AQ
DIFFERENTIAL
LOW (AQD.L)

AQ
DIFFERENTIAL
HIGH (AQD.H)

DIFFERENTIAL

C09145

Fig. 8 -- Economizer Minimum Position

If the indoor fan is not operating, the economizer will be fully

closed, 0% open.
Ventilation Mode
If the space temperature falls 0.5F below the Occupied Cool Set
Point (SetpointsOCSP) the compressor will turn off, the indoor

fan speed will be set to the Vent Mode Fan Speed

(ConfigurationUNITFS.VM) and the economizer will open

to the position that will supply minimum ventilation air at the

configured

Vent

Mode

Fan

Speed

(ConfigurationUNITFS.VM). Default Vent Mode Fan Speed

(ConfigurationUNITFS.VM) is 50%. Configuring the Vent

Mode Fan Speed (ConfigurationUNITFS.VM) lower will

provide additional energy savings in vent mode but may not

supply the required ventilation air to the conditioned space at lower
fan speeds.
Demand Control Ventilation
The 48PD units can also be equipped with optional CO

2

sensors

for additional indoor air quality control. When unit is equipped
with a return duct CO

2

sensor or return duct CO

2

sensor and

outside air CO

2

sensor the Economizer minimum position vs. fan

speed curve will be recalculated based on the CO

2

level of the

return and/or outside air as shown in Fig. 8. See the Indoor Air