Table 8 — ComfortLinkAlarm Codes

ALARM

OR

ALERT

NUMBER

DESCRIPTION

ACTION TAKEN BY

CONTROL

RESET

METHOD

PROBABLE CAUSE

T051

Digital Compressor Control Board Alarm

No action

Automatic

See the DSC’s LEDs for troubleshooting

Compressor A1 Safety Trip

Add Strike for Circuit A

Automatic

Current Sensing turned on (CS.A1 = Enable) and

should be off

Service Test --- Compressor A1 Safety Trip

Add Strike for Circuit A

Automatic

Current Sensing turned on (CS.A1 = Enable) and

should be off

Compressor A1 Current Detected After

Turnoff

Turn off all

compressors

Automatic

Current Sensing turned on (CS.A1 = Enable) and

should be off

Service Test --- Compressor A1 Current

Detected After Turnoff

Turn off all

compressors

Automatic

Current Sensing turned on (CS.A1 = Enable) and

should be off

T064

Circuit A Saturated Condensing Temp

Thermistor Failure

Use OAT to control

Outdoor fans

Automatic

Faulty, shorted, or open thermistor caused by wiring

error or loose connection.

T066

Circuit A Saturated Suction Temperature

Thermistor Failure

No Cooling

Automatic

Suction transducers internally forced inactive

T073

Outdoor Air Temperature Thermistor Failure

No cooling with

economizer

Automatic

Faulty, shorted, or open thermistor caused by wiring

error or loose connection.

T074

Space Temperature Thermistor Failure

No heating or cooling

Automatic

Faulty, shorted, or open thermistor caused by wiring

error or loose connection.

T075

Supply Air Temperature Thermistor Failure

No cooling mode

Automatic

Faulty, shorted, or open thermistor caused by wiring

error or loose connection.

T076

Return Air Thermistor Failure

No differential DB

crossover

Automatic

Faulty, shorted, or open thermistor caused by wiring

error or loose connection.

T077

Space Relative Humidity Sensor Failure

If RH.S = Yes, then no

indoor humidity control

Automatic

Faulty, shorted, or open sensor caused by wiring

error or loose connection.

T092

Circuit A Suction Pressure Transducer

Failure

Shutdown Circuit A

Manual

Faulty transducer, faulty 5---V power supply, or loose

connection

T102

Compressor A1 Current Sensor Failure

If CS.A1 = Enable,

then no T051 current

alarm

Automatic

Current Sensing turned on (CS.A1 = Enable) and

should be off

T110

Circuit A Loss of Charge

Shutdown Circuit A

Manual

Low refrigerant or faulty suction pressure transducer

Service Test --- Circuit A Loss of Charge

Shutdown Circuit A

Manual

Low refrigerant or faulty suction pressure transducer

T126

Circuit A High Discharge Pressure

Shutdown Circuit A

Automatic

An overcharged system, high outdoor ambient

temperature coupled with dirty outdoor coil, plugged

filter drier, or a faulty high---pressure switch.

Service Test --- Circuit A High Discharge

Pressure

Shutdown Circuit A

Automatic

An overcharged system, high outdoor ambient

temperature coupled with dirty outdoor coil, plugged

filter drier, or a faulty high---pressure switch.

T133

Circuit A Low Refrigerant Pressure

Add Strike for Circuit A

Automatic

Low refrigerant charge, dirty filters, evaporator fan

turning backwards, loose or broken fan belt, plugged

filter drier, faulty transducer, excessively cold return

air, or stuck open economizer when the ambient

temperature is low.

Service Test --- Circuit A Low Refrigerant

Pressure

Add Strike for Circuit A

Automatic

Low refrigerant charge, dirty filters, evaporator fan

turning backwards, loose or broken fan belt, plugged

filter drier, faulty transducer, excessively cold return

air, or stuck open economizer when the ambient

temperature is low.

T143

Circuit A Failure To Pressurize

Add Strike for Circuit A

Automatic

Wiring causing reverse rotation or faulty compressor

Service Test --- Circuit A Failure To

Pressurize

Add Strike for Circuit A

Automatic

Wiring causing reverse rotation or faulty compressor

T153

Real Timeclock Hardware Failure

No time and date

schedule operation

Automatic

No time/date configured, software failure, or MBB

failure

A154

Serial EEPROM Hardware Failure

Unit Shutdown

Automatic

Software failure or MBB failure

T155

Serial EEPROM Storage Failure Error

Unit operation errors

Automatic

Software failure or MBB failure

A156

Critical Serial EEPROM Storage Fail Error

Unit Shutdown

Automatic

Software failure or MBB failure

A157

A/D Hardware Failure

Unit Shutdown

Automatic

Software failure or MBB failure

A163

Circuit A Down Due to Failure

Shutdown Circuit A

Manual

Circuit has 3 strikes or has been locked out by

another alarm

Service Test --- Circuit A Down Due to

Failure

Shutdown Circuit A

Manual

Circuit has 1 strike or has been locked out by another

alarm