Integrated Gas Control (IGC) Board

The IGC is provided on gas heat units. (See Fig. 21 and Table 24.)
The IGC controls the direct spark ignition system and monitors the

rollout switch, limit switch, and induced-draft motor Hall Effect

switch.

The IGC is equipped with an LED (light-emitting diode) for
diagnostics. See the Troubleshooting section for more information.

RED LED-STATUS

C07028

Fig. 21 -- Integrated Gas Control (IGC) Board

Table 24 — IGC Connections

TERMINAL

LABEL

POINT DESCRIPTION

SENSOR LOCATION

TYPE OF I/O

CONNECTION

PIN NUMBER

INPUTS

RT, C

Input power from TRAN 1

control box

24 VAC

SS

Speed sensor

gas section

analog input

J1, 1---3

FS, T1

Flame sensor

gas section

switch input

W

Heat stage 1

MBB

24 VAC

J2, 2

RS

Rollout switch

gas section

switch input

J2, 5---6

LS

Limit switch

gas section

switch input

J2, 7---8

CS

Centrifugal switch (not used)

switch input

J2, 9---10

OUTPUTS

L1, CM

Induced draft combustion motor

gas section

line VAC

IFO

Indoor fan request

control box

relay

J2, 1

GV (W1)

Gas valve (heat stage 1)

gas section

relay

J2, 12

GV (W2)

Gas Valve (heat stage 2, from MBB)

gas section

Not on IGC