Temperature compensated start – Carrier 48/50PD05 User Manual

Page 22

Advertising
background image

22

will not be interrupted to the burners and heating will continue.
Once modified, the fan on delay will not change back to 45

seconds unless power is reset to the control. When the indoor fan
turns on after the 40 or 45 second delay the indoor fan will run at

100% fan speed.
Gas Heat Staging
When additional heat is required, power is supplied to the second

stage of the main gas valve. When the space temperature is 0.5F
above the Occupied Heat Set Point (SetpointOHSP) or

Unoccupied Heat Set Point (SetpointUHSP) power is removed

from the second stage of the main gas valve and to the IGC W1

terminal. Both stage 1 and stage 2 of the gas valve closes,

interrupting the flow of gas to the main burners.
Gas Heat Shut Down
If power to the IGC W1 terminal lasted less than 1 minute, the

heating cycle will not terminate until 1 minute after power is

applied to the W1 terminal of the IGC board.

If the over

temperature limit opens after the indoor motor is stopped within 10

minutes of W1 becoming inactive, on the next cycle the time will
be extended by 15 seconds. The maximum delay is 3 minutes.

Once modified, the fan off delay will not change back to 45

seconds unless power is reset to the control. A LED indicator is
provided on the IGC to monitor operation. The IGC is located in

the gas burner section and can be accessed by opening the gas
access door. During normal operation, the LED is continuously

on.
Gas Heat with Economizer
When there is a call for heat as described above the indoor fan will
operate

at

the

Supply

Fan

Maximum

Speed

(ConfigurationUNITFS.MX) configuration setting and the

economizer outdoor air damper will move to the Econ Min at Max
Fan Speed (ConfigurationECONMP.MX) position. The

economizer outdoor air damper is closed when the indoor fan is
not operating.

Electric Heating Mode Using Space Temperature

Sensor T55, T56, or T58 (50PD Units Only)

For electric heat units with factory installed electric heat, the Type

of Heat Installed (ConfigurationHEATHT.TY) will be

factory set to a value of 2 and the Number of Heat Stages

(ConfigurationHEATN.HTR) will be factory set to match the

installed heater. If electric heat is installed in the field the value for
Number of Heat Stages (ConfigurationHEATN.HTR) must

be changed to match the number of heat stages installed.
Heat will not operate if the outdoor temperature is greater that the

value configured for the Heating Lockout Temperature

(ConfigurationHEATHT.LO), Heat Minimum On Time

(ConfigurationHEATMRT.H) and Heat Minimum Off Time

(ConfigurationHEATMOT.H). Timeguards apply to both

stages of heating. Factory defaults values are 2 minute s ON and 2

minutes OFF.
If the indoor fan control is configured to cycle with the heating
demand by setting Fan ON When Occupied Heat Minimum On

Time (ConfigurationUNITOC.FN) to NO, the fan will stop

after a delay configured by Fan--off Delay, Elect Heat

(ConfigurationHEATFOD.E). The factory default for

Fan--off Delay, Elect Heat (ConfigurationHEATFOD.E) is

30 seconds.
The electronic control uses information from the space sensor to
determine the number of heat stages required. Once the number of

stages needed for heating is determined, either Heat Stage 1 Relay

(OutputsHEATHT.1),

or

Heat

Stage

1

Relay

(OutputsHEATHT.1)

and

Heat

Stage

2

Relay

(OutputsHEATHT.2) outputs will be turned on. See Gas

Heating Mode Using Space Temperature Sensor for more

information.

Supply--Air Temperature Sensor (SAT)
The

SAT

Heat

Mode

Sensing

(ConfigurationHEATSATSAT.H) affects the Supply Air

Temperature (TemperaturesAIR.TSAT) value displayed. This

configuration is accessible via the Scrolling Marquee on the SAT
Heat Mode Sensing (ConfigurationHEATSATSAT.H).
When

the

SAT

Heat

Mode

Sensing

(ConfigurationHEATSATSAT.H) =DSBL, the Supply Air

Temperature

(TemperaturesAIR.TSAT) value on the

Scrolling Marquee and the CCN tables will be forced to zero when
heat outputs come ON and for 5 minutes after. The default Supply

Air Temperature (TemperaturesAIR.TSAT) location is at the

fan inlet, upstream of the heat section.
When

the

SAT

Heat

Mode

Sensing

(ConfigurationHEATSATSAT.H) = ENBL, the Supply

Air Temperature (TemperaturesAIR.TSAT) sensor reading is

displayed at the Scrolling Marquee and the CCN tables during
heating mode. This setting should only be used if the original SAT

sensor wires are removed from the Main Base Board (MBB) and

replaced by an accessory SAT sensor located in the supply duct
downstream of the heat section. There are then two supply air

temperature limits that become active, the Maximum SAT Lower
Level (ConfigurationHEATSATSAM.L) the Maximum

SAT Upper Level (ConfigurationHEATSATSAM.U).

Any time the supply air temperature rises above the Maximum
SAT Lower Level (ConfigurationHEATSATSAM.L) the

heat staging will be limited to what is currently on and no
additional stages can be added until the supply air temperature falls

below

the

Maximum

SAT

Lower

Level

(ConfigurationHEATSATSAM.L).

If the supply air

temperature rises above the Maximum SAT Upper Level

(ConfigurationHEATSATSAM.U), then heating will be

reduced by removing a heat stage. That stage can not be added

again

until

the

Supply

Air

Temperature

(TemperaturesAIR.TSAT) falls below the Maximum SAT

Lower Level (ConfigurationHEATSATSAM.L). If the

supply air temperature stays above the Maximum SAT Upper
Level (ConfigurationHEATSATSAM.U), then another

stage will be removed after the Heat Stage Decrease Time

(ConfigurationHEATH.DEC).

Temperature Compensated Start

This logic is used when the unit is in the unoccupied state. The

control will calculate early Start Bias time based on Space
Temperature deviation from the occupied cooling and heating set

points. This will allow the control to start the unit so that the space
is at conditioned levels when the occupied period starts. This is

required for ASHRAE 90.1 compliance.

Setting Up the System

The settings for temperature compensated start can be found in the
local display under ConfigurationUNIT.

ITEM

EXPANSION

RANGE UNITS CCN POINT

TCS.C

Temp.Cmp.Strt.Cool Factr 0 --- 60

min

TCSTCOOL

TCS.H

Temp.Cmp.Strt.Heat Factr 0 --- 60

min

TCSTHEAT

Temp Comp Strt Cool Factr (TCS.C)

This is the factor for the start time bias equation for cooling.

Temp Comp Strt Heat Factr (TCS.H)

This is the factor for the start time bias equation for heating.
IMPORTANT: Temperature compensated start is disabled when
these factors are set to 0.

48/

50P

D