EVCO EVB1256N9D User Manual
Page 55
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 55 of 92
A7
0
240
min
15
15
15
15
15
15
15
15
temperature alarm delay (code “AL” and code “AH”)
A8
0
240
min
15
15
15
15
15
15
15
15
delay in maximum temperature alarm (code “AH”) from
the conclusion of evaporator fan standstill (21)
A9
0
240
min
15
15
15
15
15
15
15
15
delay in maximum temperature alarm (code “AH”)
following the deactivation of the door micro switch input
(22)
A10
0
240
min
1
not
avail.
1
not
avail.
1
not
avail.
1
duration of a power cut such to cause the power cut alarm
to be memorised (code “PF”)
A11
0.1 (5)
15.0
°C/°F
(1)
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
differential of parameters A1 and A4
A12
0
2
- - - -
not
avail.
1
not
avail.
1
not
avail.
1
not
avail.
1
type of power supply cut-off alarm signal (code “PF”)
0
=
alarm will be signalled by the “HACCP” LED
1
=
alarm will be signalled by the “PF” code, the
buzzer and the “HACCP” LED
2
=
alarm will be signalled by the “PF”
code, buzzer
(as long as cut-off duration exceeds time A10)
and by the “HACCP” LED