EVCO EVB1256N9D User Manual
Page 64
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 64 of 92
i15
0
9
- - - -
9
9
9
9
9
9
9
9
effect caused buy the activation of the multifunction input
2 (33)
0
=
no effect
1
=
ACTIVATION OF “ENERGY SAVING” FUNCTION -
the “energy saving” function will be activated (just
with effect on the compressor, until the input is
deactivated), provided the "rapid cooling" function
is not running; see also r4
2
=
ACTIVATION OF MULTIFUNCTION INPUT ALARM -
once time i7 has passed the display will show the
flashing code “iA” and the buzzer will be activated
(until the input is deactivated)
3
=
ACTIVATION
OF
THE
MAXIMUM
PRESSURE
SWITCH ALARM - the compressor will be switched
off, the condenser fan will be switched on(only if
u1 and/or u11 = 6), the display will show the
flashing code “iA” and the buzzer will be activated
(until the input is deactivated): when the input
has been activated the number of times
established with parameter i8 the regulators will
be switched off, the condenser fan will be
switched on (only if u1 and/or u11 = 6), the
display will show the flashing code “iSd” and the
buzzer will be activated (until the input is
deactivated and the device is switched off and re-
started or until the power supply is interrupted);
see also i7 and i9
4
=
SWITCHING ON THE AUXILIARY OUTPUT - the
auxiliary output will be switched on (only if u1
and/or u11 = 2, until the input is deactivated)
5
=
SWITCHING OFF THE DEVICE - the device will be
switched off (until the input is deactivated)