Program Section: P001 (Inputs)

Pxx100 Keypad Selections Note: “xx1” represents the input number.
(left to right on keypad screen) Example:

Pressing the keypad button under 

?

will display the module the point is associated with and the module’s point

range.
Default Name

Selections

Description

Example:

201

Circuit Type

0: N/C (no EOL)
1: N/C with 2.2k EOL
2:

Form “C” single resistor

EOL & N/O with 2.2k EOL
3: Form C—dual 2.2k

First digit of the input’s first 3 digit code for standard types
only. Refer to S007:00 for Custom Circuit Types.
A “000” 3 digit code is an undefined input.

Example:

201

Point Type

01 - 33: See the Input Point
Type Reference table.
80 - 99: Custom types
programmed in section: T080 -
T099.

Second 2 digits of the input’s first, 3 digit code
A “000” 3 digit code is an undefined input.

01

Area this input is
assigned to.

– –

01

Buffer Area

A secondary area that shares Entry/Exit doors with
the above first area. If not a Buffer Area, enter the
same area number as above, again here.


Pxx11 Keypad Selections (left to right on keypad screen)
Note: “xx1” represents the input number.
Default Name

Selections Description

Example:
FRONT DOOR
(16 available characters)

Input # 1
Label

The input name that will appear in input
Status, Alarm menus, etc. Edit the same
as the Greeting Message, S001:04

Input Point-Type Reference

Point Type (

###

)

Class

Monitored for these

Area Arming Level(s)

Monitoring Style

By-

pass Chime Tx Off

Tx

Stay Tx On

Sonlrt

Off

Sonlrt

Stay

Sonlrt

On

Siren

Off

Siren

Stay

Siren

On

01

(Entry Door)

Burg

Stay & On

Entry/Exit Door

02

(Entry Route)

Burg

ON Only

Entry/Exit Route

03

(Perimeter)

Burg

Stay & On

Immediate

04

(Interior Motion) Burg

ON only

Immediate

05

(Motion–FAP)

Burg

ON only

FAP

FAP: (False Alarm Preventor) If a FAP input is not OK longer than 10 seconds, an alarm condition occurs. If a FAP input is triggered and immediately resets, a 20
minute timer begins. If the same device is tripped or a different FAP device trips in the same 20 minutes, an alarm occurs.

06

(Day Warning)

Burg

24hr

Immediate

07

(24hr Burglary)

Burg

24hr

Immediate

10

(Fire - A)

Fire-A 24hr

Immediate

11

(Fire - Delayed) Fire

24hr

15s delay

12

(Fire - Immed)

Fire

24hr

Immediate

13

(Hold-up)

holdup 24hr

Immediate

14

(Aux Alert)

Emerg 24hr

Immediate

20

(Supervisory)

Spvsr 24hr

Immediate

30

(Local - 24hr)

Burg

24hr

Immediate

31

(Local-Stay&On) Burg

Stay & On

Immediate

32

(Future Use)

Burg

Future Use

Future Use

33

(Local - ON only) Burg

ON only

Immediate

80 - 99

(Custom)

Custom point types as defined in T080 - T099. Custom point types provide full control over input point characteristics, plus additional
features including arm/disarm keyswitch operation, and setting up garage door sensors, Vault/Safe class input points, plus guard-tour
points, and work-late buttons.