Monitor xL™ Advanced Installation Guide
31
Program Section: P001 (Inputs)
Pxx100 Keypad Selections Note: “xx1” represents the input number.
(left to right on keypad screen) Example:
Pressing the keypad button under
?
will display the module the point is associated with and the module’s point
range.
Default Name
Selections
Description
Example:
201
Circuit Type
0: N/C (no EOL)
1: N/C with 2.2k EOL
2:
Form “C” single resistor
EOL & N/O with 2.2k EOL
3: Form C—dual 2.2k
First digit of the input’s first 3 digit code for standard types
only. Refer to S007:00 for Custom Circuit Types.
A “000” 3 digit code is an undefined input.
Example:
201
Point Type
01 - 33: See the Input Point
Type Reference table.
80 - 99: Custom types
programmed in section: T080 -
T099.
Second 2 digits of the input’s first, 3 digit code
A “000” 3 digit code is an undefined input.
01
Area this input is
assigned to.
– –
01
Buffer Area
–
A secondary area that shares Entry/Exit doors with
the above first area. If not a Buffer Area, enter the
same area number as above, again here.
Pxx11 Keypad Selections (left to right on keypad screen)
Note: “xx1” represents the input number.
Default Name
Selections Description
Example:
“ FRONT DOOR “
(16 available characters)
Input # 1
Label
–
The input name that will appear in input
Status, Alarm menus, etc. Edit the same
as the Greeting Message, S001:04
Input Point-Type Reference
Point Type (
###
)
Class
Monitored for these
Area Arming Level(s)
Monitoring Style
By-
pass Chime Tx Off
Tx
Stay Tx On
Sonlrt
Off
Sonlrt
Stay
Sonlrt
On
Siren
Off
Siren
Stay
Siren
On
01
(Entry Door)
Burg
Stay & On
Entry/Exit Door
–
–
–
–
02
(Entry Route)
Burg
ON Only
Entry/Exit Route
–
–
–
–
–
–
03
(Perimeter)
Burg
Stay & On
Immediate
–
–
–
04
(Interior Motion) Burg
ON only
Immediate
–
–
–
–
–
–
05
(Motion–FAP)
Burg
ON only
FAP
–
–
–
–
–
–
FAP: (False Alarm Preventor) If a FAP input is not OK longer than 10 seconds, an alarm condition occurs. If a FAP input is triggered and immediately resets, a 20
minute timer begins. If the same device is tripped or a different FAP device trips in the same 20 minutes, an alarm occurs.
06
(Day Warning)
Burg
24hr
Immediate
–
–
–
–
–
07
(24hr Burglary)
Burg
24hr
Immediate
–
10
(Fire - A)
Fire-A 24hr
Immediate
–
–
11
(Fire - Delayed) Fire
24hr
15s delay
–
–
12
(Fire - Immed)
Fire
24hr
Immediate
–
–
13
(Hold-up)
holdup 24hr
Immediate
–
–
–
–
–
–
–
–
14
(Aux Alert)
Emerg 24hr
Immediate
–
–
20
(Supervisory)
Spvsr 24hr
Immediate
–
–
–
–
30
(Local - 24hr)
Burg
24hr
Immediate
–
–
–
–
31
(Local-Stay&On) Burg
Stay & On
Immediate
–
–
–
–
–
32
(Future Use)
Burg
Future Use
Future Use
–
–
–
–
–
–
–
33
(Local - ON only) Burg
ON only
Immediate
–
–
–
–
–
–
–
80 - 99
(Custom)
Custom point types as defined in T080 - T099. Custom point types provide full control over input point characteristics, plus additional
features including arm/disarm keyswitch operation, and setting up garage door sensors, Vault/Safe class input points, plus guard-tour
points, and work-late buttons.
201
·
01
·
01
·········
Save
? P001
00