Installation

Figure 20: 460A4 Circuit Board in Place with Connections Made

19

In the kit, locate the W172 3-wire harness for IS Barrier.

20

Place the connector on the harness on P5 of the LP-70 Polycase box (

Figure 19

).

21

Using three of the crimp splices, connect the wires of the harness to the wires extending from
the top of the IS barrier. Match color codes.

22

Connect the ground wire (wire with eyelet connector) to the nearest true ground.

23

Disconnect cable going to P6 connector of the Pump CPU board.

24

Connect the cable that was disconnected in previous step to P9 connector in the LP-70
Polycase box.

25

If the user wants to be able to display electronic totals, a second cable (C06003) must be
installed and connected to the P6 connector on the Pump CPU board.

26

In the LP-70 Polycase box, locate the DIP switches shown in

Figure 19

and set the switches

for the proper unit as shown in the following table:

DIP Switch Settings

Switch
Number

Switch Function

Settings

1

Product 1

ON for Diesel, OFF for Gasoline

2

Product 2

ON for Diesel, OFF for Gasoline

3

Not used

N/A

4

Not used

N/A

5

Pulser Multiplier

ON for 9850, OFF for 9852/9853

6

Number of Probes

ON for two (2) probes, OFF for one (1) probe

W283 Display Adapter
Connector on J4

J4

460A4 Circuit
Board Assembly