Tcp/ip socket connections – Vaisala Hydromet Data Collection Platform User Manual

Page 50

Advertising
background image

User's Guide ______________________________________________________________________

48 ___________________________________________________________________M210784EN-E

the response length affect whether or not the timeout will expire
during a request.

7.

From the COM port field, select the serial port to be used on your
computer and the line parameters. The default line parameters for
the QML logger are 9600 bps, No parity bit, 8 data bits, 1 stop bit,
No flow control.

8.

If you are using a modem to connect to the QML logger, enter also
the Telephone number to dial, the modem Initialization and Dial
commands
, and the Hangup command. For instance, in the
Initialization command field, you could enter "ATE\rATX1";
that is, multiple AT commands separated by a "\r". Likewise, in the
Dial-up command
field, you could enter ATDT123456; that is, an
AT command immediately followed by a phone number.

9.

Save your settings and return to the Address Book window by
selecting Save.

TCP/IP Socket Connections

Using TCP/IP socket to connect to the QML logger requires that the
logger setup contains a virtual COM port with matching configuration:

-

Service connection is enabled

-

Incoming connection is enabled (client socket only)

-

Port setting matches with AWS Client (client socket only)

-

Target IP and port settings match with AWS Client (server socket
only)

For further information, see section Virtual COM Port in Vaisala
HydroMet™ Data Collection Platform User's Guide, Volume 3.

If QML logger with DSE101 Ethernet piggyback does not have a valid
setup but its IP address is known, it can be connected with a client
socket connection to port 50000.

To add an Address Book entry for a TCP/IP socket connection, proceed
as follows:

1.

On the Settings menu, select Address Book.

2.

Select New. The fields for selecting new connection parameters are
displayed.

Advertising