Videotec DCT User Manual

Page 93

Advertising
background image

6.5.7

Special codes

Some parameters can be configured by inserting a special code.
Go to the page for inserting special codes (see § 6.1.5 - Layout of the configuration menus, page 76) and
insert the numeric values using the keypad.

Code

Function

AUTOPAN

301

Store the current position as the first limit switch

302

Store the current position as the second limit switch

XXX

XXX = 0 ÷ 255: autopan speed (0 = minimum, 255 = maximum)
Note: not available on the Saturn model.

PATROL

1000

Delete the Patrol sequence

1XXX

XXX = 001 ÷ 128: insert Preset position XXX in the Patrol sequence

2000

Enable the Patrol sequence

2XXX

XXX = 001 ÷ 128: delete Preset position XXX from the Patrol sequence

3XXX

XXX = 000 ÷ 255:

length of pause (in seconds) when the position is reached (dwell time)

Example

1000” deletes the previously defined sequence
1001” inserts preset position No. 1 in the sequence
1005” inserts position 5 in the sequence
1006” inserts position 6 in the sequence
2005” removes position 5
To start the Patrol sequence see § 6.5.5 -Patrol, page 90.

OTHER FUNCTIONS

4XXY

The dome can be configured to move automatically to a “return position” after a set
period of inactivity.
XX = 01 ÷ 99: “Return position (positions from No. 100 to No. 128 cannot be selected);
Y = 0 ÷ 9: Waiting time before automatic return:
0: 10 seconds, 1: 20 seconds, 2: 30 seconds,3: 40 seconds, 4: 1 minute,
5: 2 minutes,6: 5 minutes, 7: 10 minutes, 8: 20 minutes, 9: 40 minutes.

4000

Disables movement to a “return position”.

Example

4216”: movement to position 21 (XX = 21) after 5 minutes (Y = 6) of inactivity.

400

Text shown/hidden (toggle)

500

Backlight compensation on/off (toggle)

9999

Reset internal memory of dome

Page 91 of 176

MNVADCT03_0716