4. OPERATING GUIDE - DISCHARGING

4 OPERATING GUIDE - DISCHARGING

4.1 DISCHARGE CHARACTERISTICS

The lead-acid and the nickel-cadmium cells are generally assigned nominal open

circuit voltages of 2.10 volts and 1.35 volts respectively. Actual open circuit voltage at

75°F/ 25°C for a fully charged battery cell depends on state-of-charge and time

after charge.

During discharge, the voltage of the cell or battery immediately begins to decrease

because of the effective internal resistance of the cell. This includes the resistance of

the terminal posts, active material, plate lugs and grids, separators, and contact

resistance between the surface of the active material and the electrolyte. The

internal resistance increases during discharge, being greater toward the end of

discharge, when the terminal voltage is lower.

As voltage gradually becomes lower during discharge, the point of near exhaustion

is reached. At this point, the discharge voltage curve begins to drop very sharply to

a value which is of no further practical use. Usually this happens at 18-20 volts for

a 24 volt lead-acid battery and 1 volt per cell for a nickel-cadmium battery (see

Figure 4-1).

Battery manufacturers specify a cutoff voltage which the battery must exceed

during a discharge test to have acceptable capacity. The cutoff voltage varies with

the rate of discharge (the discharge current/time combination used to draw the

same capacity). For example, the minimum cutoff voltages for a 30 ampere-hour,

24-volt naval aircraft lead-acid storage battery are generally specified as is shown

in Table 4- 1.

Table 4- 1 Cutoff voltages at different discharge rates for a 30

ampere-hour, 24 volt lead-acid battery

The specified final minimum cutoff voltage represents the value of voltage at which the

rated ampere-hour capacity of the battery must have been delivered for the specified

discharge rate. Figure 4-1 is a typical discharge curve for a 40 ampere-

hour sealed lead-acid (SLAB) aircraft storage battery discharged at a 1-hour rate of