4. OPERATING GUIDE - DISCHARGING

4.2.1 Constant-Current Discharge Method

The most accurate and repeatable method of measuring capacity is to discharge the

battery at a constant-current rate. This is also the method used by the CA1550. The

load resistance in this method is continuously and automatically varied to maintain a

constant discharge current as the battery's voltage decreases. A schematic of the

circuit diagram for the CA-1550 can be seen in Figure 4-3. At the end of discharge,

the calculation of ampere-hour capacity is the product of

discharge current and the elapsed discharge time.

LOAD RESISTOR

Figure 4-3. Circuit diagram for constant current discharge test

NOTE: Always read the battery manufacturer's operating

instructions. Some lead-acid batteries are recommended at a

20 volt cutoff when tested for an hour at 80% of rated

capacity. Some nickel-cadmium battery requirements are

testing for two hours at half the rated capacity, and a 1 volt per

cell cutoff.

4.3 PREPARATION FOR TESTING

Before starting the discharge test, read the component maintenance manual

(CMM) or the operating and maintenance manual (OMM) for the specific battery to be

tested. Ensure that the discharge rate and cutoff voltage from the battery

manufacturer are followed.

It is recommended that a visual inspection of the battery is carried out in

conjunction with testing and charging batteries.