Batt, Bbs unit, 1j2/ p2 – OnLine Power Signal Saver IPC User Manual

Page 20: 11 j3/ p3, 1j4/ p4, 1j1/ p1

Advertising
background image


6002-1842 Rev A ECO# 8881

10

44

AC INPUT

& OUTPUT

CIRCUIT

BREAKER

AC INPUT

N

L

48V BATTERY

CONNECTOR

Battery temperature

Sensor

C; COMMON NC:NORMALLY CLOSED NO:NORMALLY OPEN

1

2

L

N

C

SERIAL INTERFACE

L

N

AC OUTPUTS

USB

C3

C4

C5

C6

C

NC

NO

NC

C

NC NO

C

C

NO

NC

CONTACTS MAXIMUM RATING: 1A, 240V

ESC

C1

C2

C

NO

NC

NC NO

OUTPUT

ALARM

Read the Operator's
Manual Before Installation
or servicing

+

NO

SELF
TEST

-

PTS

48VDC 3A MAX

EXTERNAL FAN

+

Heavy Object

46.2lbs, 21Kg

Warning

+

BATTERY

CIRCUIT

BREAKER

+

BATTERY VOLTAGE

TEST POINT

4

4

44

BATT

+

1

1

J2/
P2

-

3

3

2

2

4

4

+

11

J3/
P3

-

3

3

BATT

2

2

+

1

1

J4/
P4

-

3

3

BATT

22

BBS UNIT

HARNESS 7060-1162-01

+

1

1

J1/
P1

-

3

3

BATT

2

2

Interconnection between Battery and UPS Control unit

Figure 1.6

♦ Tape or seal the Battery Temperature Sensor to the case of the top battery. Plug the connector on the

other end into the BBS at “Battery Temperature Sensor”. Wrap a tie around the strain relief loop and
the battery temperature sensor to prevent the connector from disconnecting during an earthquake or
other severe vibrations.








TIP: The 48V BATTERY CONNECTOR must ‘click’ when inserted for proper connection.

A common source of problems is that the battery connector is not fully inserted. The BBS will
Alarm when turned on if the batteries are not properly connected.

NOTE: The LCD Display and keypad on the BBS are shipped with a protective plastic film

over them. This film should be removed by peeling from one corner before first use of the
system. The LCD display will be difficult to read if the film is left on.