SHUT DOWN:

1.6.1 UPS control unit Shutdown:

Step 1.

Put the By-Pass Switch in the MBS/PTR box is in the “BYPASS”
Position.

Step 2.

Turn off the battery circuit breaker.

Step 3.

Turn off the input circuit breaker.

Step 4.

Unplug the 48V EXT battery connector from the unit.

Step 5.

Disconnect the PTR control signals by un-plugging the

J2/P2

Step 6.

Disconnect the input and output wires from AC INPUT & AC OUTPUT
terminal block of the BBS unit. and isolate the wires individually using
electrical tape.

This completely removes the wire from the BBS unit.

It is now safe to remove the unit for maintenance.

MBS/PTR UNIT

Read the Operator's

N

L

N

L

L

N

AC INPUT

or servicing

Manual Before Installation

AC OUTPUTS

EXTERNAL FAN
48VDC 3A MAX

Sensor

Battery temperature

BREAKER

CIRCUIT

& OUTPUT

AC INPUT

Warning

46.2lbs, 21Kg

Heavy Object

C; COMMON NC:NORMALLY CLOSED NO:NORMALLY OPEN

NO

STEP 3

NC

C2

USB

ALARM

OUTPUT

SERIAL INTERFACE

C

NO

NC

C

C1

2

1

PTS

ESC

-

TEST

SELF

CONTACTS MAXIMUM RATING: 1A, 240V

NC NO

C

C

NO

NC

C

NC NO

NO

NC

C

C6

C5

C4

C3

+

STEP 2

CONNECTOR

TEST POINT

BATTERY VOLTAGE

+

+

BREAKER

CIRCUIT

+

48V BATTERY

BATTERY

STEP 4

STEP 5

STEP 6

BBS UNIT

DANGER!

Even when the unit is off, there are potentially dangerous voltages
within the unit due to the batteries and line power connection.
Exercise extreme care when working within the BBS system.

MANUAL BYPASS SWITCH

CABINET

POWER

GND

UTILITY

LINE

NEU

AC TO

323

3

TB1

1

2

4

BBS

BYPASS

STEP 1