OnLine Power Signal Saver IPC User Manual

Page 44

Advertising
background image


6002-1842 Rev A ECO# 8881

34

2.2.5 Manual start up on Battery/Reset

Purpose: Describes the Start Up procedure when AC power is not available.

When AC power is not available, the BBS2000 can manually be turned on and function only ON BATTERY. When
utility AC power returns, the BBS2000 will qualify the line for 30 seconds (default) and then resume normal operation in
the ON LINE mode.


This function is available only when the unit is first turned on and the LCD shows STANDBY. Verify that the AC Input
& Output
and Battery Circuit Breakers on the BBS2000 are OFF.




START

Verify that the AC input & output

and Battery Circuit Breaker on
the BBS is OFF

The BBS is now supplying AC

power to the Loads.
it will automatically resume
normal operation when utility

AC power is provided.

No further action is required to

deactivate MANUAL ON operation.

Arrow down to MANUAL ON/RESET

and Press ENTER which manually
stars the inverter and supplies
output power from batteries

Place the Manual Bypass Switch
in the BBS position

START UP FINISHED

The LCD display shows STANDBY

Turn ON AC input & output
Circuit Breaker

Turn ON the upstream

Utility input Circuit Breaker
if it is not already ON

Turn ON the Battry Circuit Breaker

Arrow down to CONTROL
submenu and press ENTER

Press ENTER key to activate the
BBS menu

Place the Manual Bypass Switch in
MBS/PTR Assy in BYPASS position

Advertising