<C4. Wiring>

C4-9

IM 01W02D01-01EN

cation cables, use shielded twisted pair cables (cables for RS-422/RS-485 communication are

recommended).

IMPORTANT

All RS-485 configuration switches are set to OFF by default. When connecting cables to the RS-

485 connector, set RS-485 configuration switches to fit actual connection before power on.

l

Connection in 4-wrie Type

YFGW410

Host System

TX+

TX-

RX+

RX-

SG

FG

TX+

TX-

RX+

RX-

SG

FG

R1

R2

R2

R1: Termination resistance of 120 Ω (comes with YFGW410)

R2: According to the instruction on the external equipment

RS-485 Configuration Switches

SW602

SW603

SW604

SW605

OFF

OFF

OFF

ON

FC0409.ai

Figure C4-7 Connection and Configuration in 4-wire Type

l

Connection in 2-wire Type

RS-485 Configuration Switches

SW602

SW603

SW604

SW605

ON

OFF

ON

ON

FC0410.ai

YFGW410

Host System

TX+

TX-

RX+

RX-

SG

FG

TX+

TX-

RX+

RX-

SG

FG

R1

R2

R1: Termination resistance of 120 Ω (comes with YFGW410)

R2: According to the instruction on the external equipment

Figure C4-8 Connection and Configuration in 2-wire Type

l

Modbus/RTU

Following table shows Modbus/RTU communication parameter of YFGW410. The host system

should be configured in accordance with following parameters.
.