Event programming – Edwards Signaling eFSA250 User Manual
Page 140

Chapter 2: Front panel programming
128
E-FSA64 and E-FSA250 Technical Reference Manual
Event programming
Panel event programming
Panel events, such as reset, system startup, and battery low have an event
notification setting for contact ID, dialer, NET, and printer, which controls where
the event is sent when it takes place. Each event has a factory default setting
that can be used with no additional programming.
Table 36: Default panel event settings
Panel event
Printer
Dialer
NET (1-8) CID
Aux. power 1 (disable)
Yes
None
No
n/a
Aux. power 1 (trouble)
Yes
Acct 1
No
312
Aux. power 2 (disable)
Yes
None
No
n/a
Aux. power 2 (trouble)
Yes
Acct 1
No
312
Battery charger (disable)
Yes
None
No
n/a
Battery charger (trouble)
Yes
Acct 1
No
309
Battery low (disable)
Yes
None
No
500
Battery low (trouble)
Yes
Acct 1
No
302
Battery missing (disable)
Yes
None
No
n/a
Battery missing (trouble)
Yes
Acct 1
No
311
Clear history
No
Acct 1
No
621
Common alarm
No
Acct 1
No
110
Common disable
No
Acct 1
No
500
Common monitor
No
None
No
n/a
Common supervisory
No
Acct 1
No
200
Common trouble
No
None
No
n/a
Common trouble for network dialer
Yes
None
No
n/a
Common trouble for telco dialer
No
Acct 1
No
373
Date
No
Acct 1
No
625
Dialer disable/remote disconnect
Yes
Acct 1
No
n/a
Dialer line 1 fault (disable)
Yes
None
No
n/a
Dialer line 1 fault (trouble)
Yes
Acct 1
No
351
Dialer line 2 fault (disable)
Yes
None
No
n/a
Dialer line 2 fault (trouble)
Yes
Acct 1
No
352