Ul 864 programming requirements – Edwards Signaling eFSA250 User Manual
Page 43

Chapter 2: Front panel programming
E-FSA64 and E-FSA250 Technical Reference Manual
31
UL 864 programming requirements
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with
the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL
864, certain programming features or options must be limited to specific values or not used at
all as indicated below.
Programmable
feature or option
Permitted in
UL 864 (Y/N)
Possible
settings
Settings
permitted in UL
864
Panel default
AC fail delay
Y
0 to 15 hours
1 to 3 hours
3 hours
Telephone line cut
supervision
duration
Y
1 to 120 seconds 10 to 120
seconds
120 seconds
Telephone line
ground fault
Y
Disabled
Enabled
Enabled
Enabled
Transmission test
frequency
Y
0 to 45 days
1 (daily)
1 (daily)
Dialer mode
Y
Dual line
Single line
Modem only
None
Dual line
Single line [2]
Modem only [3]
None [3]
Dual line
Dialer retries
Y
5 to 10
5 minimum
5 retries
Dialer retry time
Y
1 to 45 seconds Yes
5 seconds
Send event restore
codes
Y
No
Yes
Yes
Yes
Swinger shutdown N
Off
1 to 255
Off
Off
Zone resound
Y
On
Off
On
On
[1] Allowed only if the IDC is connected to the latching alarm device
[2] Allowed only when the supervising station supervises the telephone line and annunciates
fault conditions within 200 seconds
[3] Prohibited when the control panel is connected to a supervising station