Edwards Signaling eFSA250 User Manual
Page 226
Advertising

Appendix B: Worksheets
214
E-FSA64 and E-FSA250 Technical Reference Manual
Worksheet B: Auxiliary/smoke power current load
Devices
Qty
Standby
current
(mA)
Alarm
current (mA)
Qty x
Standby
current (mA)
Qty x Alarm
current (mA)
RPM
20
270
E-2WIRE [1]
17
58
RLCD(F)
98
113
RLCD-C(F)
99
115
RLED-C(F)
28
62
LED24
6
34
Totals (mA)
(transfer totals to Battery Calculation Worksheet)
[1] Enter 1 regardless of how many are installed. Only the first E-2WIRE in the alarm state
draws current. The other ones do not because the system load sheds additional modules in
alarm.
Advertising