Option
Description
bases only).
None: A correlation group triggers the base. It can be applied to both relay
and sounder bases and is used for relay bases configured as latched
output devices.
Note:
All base follow settings except Head and Riser can be activated by
correlation groups.
[1] Not all options listed here are displayed on all systems.
Dialer options
Table 21 describes the options used to set up the dialer.
Table 21: Auto programming — Dialer options [1]
Option
Description
Account 1
Account ID:
Enter the four-digit ID code for
account 1 Note, if you do not change the default
of FFFF, no events will be sent.)
Primary receiver number: Enter the primary
receiver’s phone number. Up to 20 digits (0-9, *, #,
and ,). The comma causes a two-second delay in
dialing. The number or hash symbol (#) and the
asterisk symbol (*) are used with calling feature
codes and services. Consult your telephone
service provider.
Secondary receiver number: Enter the secondary
receiver’s phone number. Up to 20 digits (0-9, *, #,
and ,). The comma causes a two-second delay in
dialing.
Format: CID
CID: Contact ID is the alarm format that the
monitoring facility (DACR) will receive. See
“Default contact ID event codes” on page 40.
Event notification: Set event notification (event
reporting) to:
Device: Only device information is reported or
transmitted, no zone information. This setting uses
default device event notification settings for
reporting events. See “Factory default settings” on
page 36.
Zone: When a device is a member of a zone, only
the zone information is reported or transmitted, no
device information. This setting uses default zone
event notification settings for reporting events.
Account 1
Account ID 6769
Primary Recver# >
Secondary Recver# >
Account 2
Account ID 6769
Primary Recver# >
Secondary Recver# >
Format CID<>
Event Notif. Event>
-------------------