Edwards Signaling eFSA250 User Manual
Page 146

Chapter 2: Front panel programming
134
E-FSA64 and E-FSA250 Technical Reference Manual
Common trouble event programming
The common trouble event can be assigned to a correlation group and turn on an
output device. When the common trouble is assigned to a correlation group,
every output device in the correlation group turns on. Event notification can also
be programmed for the common trouble.
Notes
• Every trouble event turns on the output devices in the correlation group it is
assigned to, so make sure you are not assigning the common trouble to an
output group that turns on devices that you do not want to turn on (e.g.
NACs).
• If you assigned a NAC and the common trouble event to a correlation group
and the NAC goes into trouble, when the NAC trouble clears the NAC outputs
do not turn off even though the common trouble condition cleared because
the NACs are not supervised. To turn off the NAC outputs, you must manually
restore the NAC from the front panel’s Control menu option.
To program the common trouble event:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2
password.
3. Choose Common Trouble.
4. Choose Trouble.
5. Choose Correlation Groups.
6. Enter the correlation group number to be
programmed. (Values range from 001 to 199.).
7. Select Yes to add the common trouble to the
correlation group or No to not add the common
trouble to the correlation group.
8. Repeat steps 8 and 9 until the common trouble is
added or removed from each correlation group
needed.
9. Choose Save.
10. Choose Event Notification.
11. Choose Trouble.
12. Set trouble event notification.
Printer: Yes or No. This controls whether event
Advanced Program
Loop Events
Unconfigured Alarm
Common Trouble
Common Trouble
Trouble
Common Trouble
Correlation Groups
Event Notification
Correlation Groups
Group 001
Status Included
Enter Exit
Trouble
Printer Yes<>
Code 10-10-10-10
Dialer Account 1&2
CID 110
NET(1-8) Yes
Save