Edwards Signaling eFSA250 User Manual
Page 274

Appendix D: Applications
262
E-FSA64 and E-FSA250 Technical Reference Manual
Figure 58: Typical wiring for a zone alarm signaling application
TB1
TENS
ONES
TB2
12
11
10
9
4
3
2
1 0
8
5 6 7
0 9
1
8
2
7
3
6
4 5
S
IG
+
S
IG
-
D
AT
A
- O
U
T
D
AT
A
- I
N
D
AT
A
+
IN
/O
U
T
S
IG
+
S
IG
-
D
AT
A
- O
U
T
D
AT
A
- I
N
D
AT
A
+
IN
/O
U
T
RED
WHT
47 k
EOLR
Ω
Double screw
terminal block
(supplied by installer)
12
11
10
9
4
3
2
1 0
8
5 6 7
0 9
1
8
2
7
3
6
4 5
PAM-1
SLC_IN+
SLC_IN-
NORMALACTIVE
-
+
+
-
24 VDC+
24 VDC-
AUX RISER
FIRST DETECTOR
SB4U
LAST DETECTOR
SB4U
BLU
ORG
Programming for zone alarm signaling
This application requires that you group your detectors into zones and correlate
outputs for each zone. The following instructions are for Zone 1 but apply for all
zones as well.
1. Set the panel’s Event Notification option to Zone.
2. Configure the smoke detectors in Zone 1 as follows:
Device Type: Smoke or Smoke Heat depending on the detector model
Message Line 1: SMOKE_<N>, where <N> can be the device address or
other number
Message Line 2: ZONE_01
Base Type: Sounder
Follow: None, Head, Alarm, Alm + Vrfy, or Alm + PreAlm
3. Configure the RLY module as follows:
Device Type: Relay Silence
Message Line 1: ZONE_1
Message Line 2: SOUNDERS
4. Configure the IDC1B module as follows:
Device type: Monitor