Installation, 6 installation recommendations for liquids, 1 general requirements – KROHNE OPTIFLEX 1300C EN User Manual

Page 24

Advertising
background image

3

INSTALLATION

24

OPTIFLEX 1300 C

www.krohne.com

03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en

3.6 Installation recommendations for liquids

3.6.1 General requirements

Clearance between the probe and other objects in the tank

Figure 3-10: Installation recommendations for liquids

1 The electromagnetic (EM) field generated by the device. It has a radius of R

min

. Make sure that the EM field is clear of

objects and product flow. Refer to the table that follows.

2 If there are too many objects in the tank, install a bypass chamber or stilling well.
3 Keep the probe straight. If the probe is too long, shorten the probe length. Make sure that the device is configured with

the new probe length. For more data on the procedure, refer to

How to decrease the length of probes

on page 98.

4 Empty space. Refer to the table that follows.

INFORMATION!
If the device has to measure the level of dangerous products (ammonia etc.), we recommend
that you use a device with the Metaglas

®

option.

Probe type

Empty space (radius, R

min

), around the probe

[mm]

[inches]

Coaxial

0

0

Double rod / cable

100

4

Single rod / cable

300

12