Operation – KROHNE OPTIFLEX 1300C EN User Manual

Page 75

Advertising
background image

OPERATION

6

75

OPTIFLEX 1300 C

www.krohne.com

03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en

7

Tank Shapes

The Wizard adds this step if you

select "Yes" in step 4. This sub-

procedure uses the

information given here to find

the volume. You have to type in

the tank shape, height, width

and length.

...

...

8

Conversion Unit

The conversion unit is given as

a volume if the product density

is given. If not, choose a mass

unit.

m3, L, US gal, GB gal, ft3,

bbl or Tons, kg, US Tons, GB

Tons

m3 or Tons

9

Mass Table

A table that converts product

level to product mass. If you

selected "Yes" in step 4, make

entries in the table in volume

units. Push[







] or [







] to

select a line and push [>>>>] to

change values automatically

supplied by the device.

Sub-

menu

Conversion

submenu

[Free Unit]

[Free Unit]

[Free Unit]

[Free Unit]

If you cannot find the units or

tank shape in the menu, you

can customize the conversion

table.

-

1

Do you want to use

a free unit?

Select "Yes".

Yes, No

2

Custom. Length

Unit

A non-standard length unit for

the conversion table. This is

defined by the supervisor.

FREE_UNIT

3

Custom. Length

Ratio

The conversion factor between

the length unit selected in

C.5.1.4 (length unit) and C.5.1.7

(customer length unit). This

ratio is a multiple of 1 mm.

min-max: 1…99999

1

4

Custom. Conv. Unit A non-standard conversion unit

for the conversion table. This is

defined by the supervisor.

FREE_UNIT

5

No. of Entries

The number of lines in the

conversion table.

min-max: 0…50

2

6

Volume/Mass

Table

A table that converts product

level to another physical

parameter. Push[







] or [







] to

select a line and push [>>>>] to

change values.

...

Current changes

must be saved or

cancelled before

proceeding

Save, Cancel

4

Save

A.1.5

A.1.5

A.1.5

A.1.5

Outputs

Outputs

Outputs

Outputs

Follow this procedure to

Follow this procedure to

Follow this procedure to

Follow this procedure to

describe the output

describe the output

describe the output

describe the output

characteristics.

characteristics.

characteristics.

characteristics.

1

Output 1: Output

Function

Select an output function to

scale the current values

(output 1). This is not displayed

in the operator mode.

1 solid/liquid:

1 solid/liquid:

1 solid/liquid:

1 solid/liquid: Level,

Distance, Volume (Mass),

Ullage Volume; 2+ liquids:

2+ liquids:

2+ liquids:

2+ liquids:

Interface Level, Interface

Distance, Interface Volume,

Layer, Layer Volume

Level

2

Output 1 (HART):

<Function> 4 mA

This assigns a measurement

value to 4 mA (output 1).

min-max:

0…20 m / 0…65.62 ft

0 m / 0 ft

Menu
No.

Step

Function

Function description

Selection list

Default

Advertising