1 module status displays, Module status displays ( 85), Module status displays – Lenze E84AYCET EtherCAT MCI module User Manual

Page 85: 11 diagnostics

Advertising
background image

Lenze · E84AYCET communication module (EtherCAT) · Communication Manual · DMS 5.0 EN · 05/2013 · TD17

85

11

Diagnostics

11.1

LED status displays

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

11.1.1

Module status displays

The LEDs MS, ME and DE show the module status.

[11-1] LEDs MS, ME, DE

E84YCET006

ME

DE

MS

LED

Colour

State

Description

MS

green

on

The communication module is supplied with voltage and is

connected to the standard device.

blinking

The communication module is supplied with voltage, but has no

connection to the standard device (the standard device is switched

off, in the initialisation phase, or not available).

ME

red

on

An error has occurred in the communication module.

DE

red

on

The communication module is not accepted by the standard device,

or the standard device is not active. (See notes in the documentation

for the standard device).

200 ms

200 ms