Diagnostic word

Operating Manual PNOZmulti communication interfaces
1001154-EN-13

137

}

Sequential muting, parallel muting, cross muting

Bit/

DW

Message

Comment

DW =

0

Enable triggered

Bit 0

Optical safety device was triggered, although muting

is inactive.

Lght curtain interrupted (without active mut-

ing), resets muting after error or starts mut-

ing

Bit 2

Safety device is ready for reset.

Waiting for reset (reset)

Bit 3

There is an object in the muting zone or the optical

safety device is faulty.

Sensor status implausible, override required

Bit 8

Cannot switch on because the start enable (“EN2”)

has not been triggered.

Muting time exceeded, only one sensor op-

erated

Bit 9

Cannot switch on because the static enable (“EN1”)

has not been triggered.

Feasibility error, muting sensors 1 and 2

Bit 10 Press was stopped because the static enable (“EN1”)

is missing.

Feasibility error, muting sensors 3 and 4,

not in the case of cross muting

}

Group diagnostic message

Bit/

DW

Message

Comment

Bit 1

Stored status of the first configured diagnostic bit

available to the OR connection

Bit 2

Stored status of the second configured diagnostic bit

available to the OR connection

Bit 3

Stored status of the third configured diagnostic bit

available to the OR connection

Bit 4

Stored status of the fourth configured diagnostic bit

available to the OR connection

Bit 5

Stored status of the fifth configured diagnostic bit

available to the OR connection

}

Press element: Run monitoring

Bit Message

Comment

2

Run monitoring is ready for reset.

Apply 1/0 pulse edge at Reset input param-

eter.

8

Start-up time was exceeded.

The set start-up time has elapsed.

9

Shaft is broken

- The camshaft is no longer mechanically

connected to the shaft
- Open circuit in the encoder circuit