6.5

EMC-compliant wiring

6

Wiring

6.5.2

Shielding

Shielding

6-

][EMV_Schirmung

Shielding measures reduce noise energy (immunity of adjacent systems
and devices to external influences):

Correct shielding of the following cables avoids interference coupling
with
– Motor cables
– Cables to the external brake resistor
– Encoder cables
– Cables with digital and analogue signals
– Cables to communications interfaces

All shielded cables are to be attached at both ends to the shield ter-
minals provided or should be connected to the connector housing.

Use cables with braided screening, with a minimum cover area of 80 %.

Any interruptions to the shielding e.g. at terminals, contactors,
chokes, should be bridged at low impedance over a wide area.

All connectors or sockets should be fastened with screws to ensure
ample, conductive contact between the braided shield and the front
plate.