7. ALARM MANAGEMENT

7.1 Storage of data/errors

The appliance electronic controller is equipped with a system of acoustic and visual signals to indicate the

intervention of safety devices. The table below gives a list of the alarms shown on the panel display

7.2 The software controls the following alarms:

Evaporator probe alarm (ALL 01)

Cause:

Exit from operating range (-58°F / -50°C - 212°F / +100°C) for over 30 seconds.

Probe is defective (REPLACE PROBE).

Beeper:

Activated (3 seconds, then a pause of 30 seconds) until the mute button is pressed.

Display:

Alternates message “ALL 01” with standard display

Reset:

Automatically resets only when probe reading has returned to normal.

Core probe alarm (ALL 02)

Cause:

Exit from operating range (-58°F / -50°C - 212°F / +100°C) for more than 30 seconds during

current chilling cycle by temperature.

Effect:

Interruption of current chilling cycle by temperature and automatic start-up of timed chilling

cycle. Chilling by temperature push-button disabled.

Probe is defective (REPLACE PROBE).

Beeper:

Activated (3 seconds, then a pause of 30 seconds) until the mute button is pressed.

Display:

Alternates message “ALL 02” with standard display

Alarm relay: Not activated.

Reset:

Press the mute push-button (with beeper off).

Resets automatically if probe value returns to normal, but cycle remains in timed mode.

Alternatively, switch off the panel then turn it back on (stand-by).

Compartment probe alarm (ALL 03)

Cause:

Exit from operating range (-58°F / -50°C - 212°F / +100°C) for over 30 seconds.

Probe is defective (REPLACE PROBE).

Effect:

Any current chilling cycle is interrupted.

If a storage phase is in progress, the compressor and the fan set to stand-by status.

When the appliance is in Stop status, press Start to set the compressor and fan to stand by.

Beeper:

Activated (3 seconds, then a pause of 30 seconds) until the mute button is pressed.

Display:

Alternates message “ALL 03” with standard display

Reset:

Automatically resets only when probe reading has returned to normal.