Input SW2 (ALL 05) (door microswitch alarm)

Cause:

Input active for more than 5 minutes with appliance in start status.

Door open (close door) Microswitch fault (replace the microswitch)

Beeper:

Activated (3 seconds, then a pause of 30 seconds) until the mute button is pressed.

Display:

Alternates message “ALL 05” with standard display

Reset:

Press the mute push-button (with beeper off).

Automatically resets if input value returns to normal Alternatively, switch off the panel then

turn it back on (stand-by).

Input SW1 alarm (ALL 06) (T5 and T14D models only)

(High pressure switch) for all models

(Compressor thermal-magnetic switch) if installed

(Oil diff. pressure switch) if installed

Cause:

Input active for more than 5 seconds

Effect:

Sets the appliance to STOP.

Reset the max. pressure switch, thermal-magnetic switch or differential pressure switch.

Beeper:

Activated (3 seconds, then a pause of 30 seconds) until the mute button is pressed.

Display:

Alternates message “ALL 06” with standard display

Reset:

Press the mute push-button (with beeper off) with no alarm cause displayed

Input SW3 alarm (ALL 08)

(Kriwan compressor automatic reset) only for T14D

(Thermostat on the discharge line)

Cause:

Input active for more than five seconds at least three times when appliance is in start mode

Effect:

Compressor shuts down and resumes operation when input value returns to normal.

The appliance sets to STOP at third alarm.

Beeper:

Activated (3 seconds, then a pause of 30 seconds) until the mute button is pressed.

Display/Led: Alternates message “ALL 08” with standard display

Reset:

Press the mute push-button (with beeper off).

Alternatively, switch off the panel then turn it back on (stand-by).

Input Ht1 alarm (ALL 09) (Input in voltage 1 ... fuses).

Input Ht2 alarm (ALL 10) (Input in voltage 2 ... fuses)