Accessing embedded web server and fusionlive – Innotech IG04 BACnet Gateway User Manual

Page 11

Advertising
background image

Installation Instructions for Innotech IG04 BACnet Gateway and Vaisala Transmitter / Sensor

Page 11

© Mass Electronics Pty Ltd 2011

Edition 5.0 dated 11/11/2013

Accessing Embedded Web Server and FusionLIVE

The Vaisala device and IG04 BACnet Gateway can be configured using the embedded web server

and the FusionLIVE Java application on the IG04. However before you can access the embedded

web server, your computer must be configured to be on the same network range as the IG04 BACnet

Gateway. The default Ethernet settings for the IG04 BACnet Gateway are shown in Table 3 below.

Table 3: 

IG04 BACnet Gateway Default Ethernet Settings

IP address

Gateway

Subnet mask

Port Number

192.168.2.100

0.0.0.0

255.255.255.0

80

Since the default IP address of the IG04 BACnet Gateway is 192.168.2.100, your computer must be

configured with an IP address in the range of 192.168.2.xxx, and the subnet mask must be configured

to 255.255.255.0. When you have configured the IP address and subnet mask of your computer, you

can access the web server using Microsoft Internet Explorer

®

Web Browser Version 8 or greater.

Follow the instructions below to connect to the IG04 BACnet Gateway and access the embedded web

server.

Launch Internet Explorer and enter the default IP address of the IG04 BACnet Gateway in the address

bar and press

Enter, as illustrated in Figure 5 below.

Figure 5:  Access embedded web server using default IP address

Please note that the Java Runtime Environment (JRE) must be installed on your computer in order to access

the embedded web server and the FusionLIVE application. The latest version of JRE can be downloaded from

http://java.com/en/

.

NOTE

For more information on configuring your computer network settings and configuring the IG04 BACnet Gateway, refer

to

DS99.05 Ethernet Setup Manual for Device Communications

.

NOTE

http://192.168.2.100/

Figure 6:  Access embedded web server using IP address with a different port

http://192.168.2.100:90

If you changed the port number in the

Ethernet Settings

, you must specify the port number with the

IP address when entered into the address bar, as illustrated in Figure 6 below.

Advertising