The 16mm, Ig04 default settings, Bacnet/ip – Innotech IG04 BACnet Gateway User Manual
Page 6
Installation Instructions for Innotech IG04 BACnet Gateway and Vaisala Transmitter / Sensor
Page 6
© Mass Electronics Pty Ltd 2011
Edition 5.0 dated 11/11/2013
Figure 2: Wiring guide for Vaisala device M12 Connector with split cabling for heating
The 16mm
2
Copper Cable to Earth Ground cable is a critical component for the correct operation of the surge protector.
Ensure this is installed correctly.
NOTE
Wiring Using The 8-Pin M12 Connector With Split Cabling For Heating
The wiring example provided below at Figure 2 is an alternative M12 connector wiring guide,
providing a shared cabling run of suitable high capacity cable for the Vaisala device and heating
accessory (if required). The pin connections for the 8-Pin M12 and wire colours are listed in Table 1 on
.
For installations that do require the optional heating accessory, ensure a high capacity cable
between the DC Power supply and the Vaisala device is used.
The 8-Pin M12 connector is located on the bottom of the Vaisala device.
NOTE
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Ethernet
&
BACIP
+
-
SHLD
24V to 32V DC
@ < 200mA
*
2
@ < 800mA
*
3
-
+
Isolated DC
Power Supply
Earth Ground
Ethernet
Port &
BACnet/
IP Output
SHLD
EOL
C+
C-
SER Terminal Not Used
(Service Tool Connection)
WSP150 Surge Protector
*
1
*
1
Wire WXT520 / WMT52 Device to the
WSP150 Surge Protector in accordance with
appropriate Vaisala technical documentation
Innotech IG04
BACnet Gateway
BL
K
W
ire
(V
in
−)
R
ED
W
ire
(V
in
+)
24V
0V
Shielded cable length should NOT exceed
3m when connecting WXT520 / WMT52
Device to WSP150 Surge Protector
If a surge protector is not installed, connect the cables directly
RS485 [+]
S
RS485 [-]
RS485 [
Shield
]
RS485 Line
Termination
Jumper
+
-
*
2
When heating is NOT used.
BLU Wire (RX−)
GRY Wire (RX+)
Only used when
heating is required
1
2
3
4
5
6
7
8
YE
L
(V
h+
)
PN
K
(V
h−
)
R
ED
W
ire
(V
in
−)
BR
N
W
ire
(V
in
+)
*
1
*
3
When heating IS used.
If heating is required and supplied via the
same supply wires, ensure a substantial cable
with cross-section > 1mm
2
is used to avoid
excessive voltage drops. Excessive voltage
drops may cause comms problems.
Note: Colour coded as per
Vaisala documentation
G
R
Y
W
ire
(R
X+
)
BL
U
W
ire
(R
X−
)
Vaisala WXT520 Weather Transmitter / WMT52 Ultrasonic Wind Sensor
M12 connector pin-out
*
1
IG04 Default Settings
IP Address: 192.168.2.100 (Static)
S/M: 255.255.255.0
Innotech Port: 20000
BACnet/IP
BACnet Port: 47808
BACnet Instance: 1509
Baud Rate: 19200
Fault Timeout: 30 Sec
HTTP Port: 80
16mm² Copper Cable
SER
WXT
MSTP
IG04 Default Settings
IP Address
192.168.2.100 (Static)
Subnet Mask
255.255.255.0
HTTP Port
80
Innotech Port
20000
BACnet/IP
BACnet Port
47808
BACnet Instance
1509
Baud Rate
19200
Fault Timeout
30 seconds