The 16mm, Ig04 default settings, Bacnet/ip – Innotech IG04 BACnet Gateway User Manual

Page 9

Advertising
background image

Installation Instructions for Innotech IG04 BACnet Gateway and Vaisala Transmitter / Sensor

Page 9

© Mass Electronics Pty Ltd 2011

Edition 5.0 dated 11/11/2013

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

Ethernet

&

BACIP

+

-

SHLD

-

+

Isolated DC

Power Supply

Earth Ground

Ethernet

Port &

BACnet/

IP Output

SHLD

EOL

C+

C-

SER Terminal Not Used

(Service Tool Connection)

WSP150 Surge Protector

*

1

Vaisala WXT520 Weather Transmitter /

WMT52 Ultrasonic Wind Sensor

Screw Terminal connector pin-out

*

1

Innotech IG04

BACnet Gateway

BL

K

W

ire

(V

in

−)

R

ED

W

ire

(V

in

+)

24V

0V

Shielded cable length should NOT exceed

3m when connecting WXT520 / WMT52

Device to WSP150 Surge Protector

If a surge protector is not installed,

connect the cables directly

RS485 [+]

S

RS485 [-]

RS485 [

Shield

]

RS485 Line

Termination

Jumper

+

-

BLU Wire (RX−)

GRY Wire (RX+)

Only used when

heating is required

YEL (Vh+)

PNK (Vh− )

RED Wire (Vin−)

BRN Wire (Vin+)

*

1

5 RXD
6 SGND
7 EXH
8 EXL
9 SIPB
10 SIPA
11 SR-
12 SR+
13 PT-
14 PT+
15 AGND
16 AGND
17 HTG-
18 HTG+
19 VIN-
20 VIN+

1 RX-
2 RX+
3 TX-
4 TX+

WXT520 / WMT52

Screw Terminals

BLU Wire (RX−)

GRY Wire (RX+)

24V to 32V DC

@ < 200mA

*

²

@ < 800mA

*

3

Note: Colour coded as per

Vaisala documentation

*

1

Wire WXT520 / WMT52 Device to the

WSP150 Surge Protector in accordance with

appropriate Vaisala technical documentation.

*

2

When heating is NOT used.

*

3

When heating IS used.

If heating is required and supplied via the

same supply wires, ensure a substantial cable

with cross-section > 1mm

2

is used to avoid

excessive voltage drops. Excessive voltage

drops may cause comms problems.

IG04 Default Settings

IP Address: 192.168.2.

S/M: 255.255.255.0

Innotech Port: 20000

BACnet/IP

BACnet Port: 47808

BACnet Instance: 1509

Baud Rate: 19200

Fault Timeout: 30 Sec

16mm² Copper Cable

HTTP Port: 80

SER

WXT

MSTP

Wiring Using The Screw Terminal Connector With Split Cabling For Heating

The wiring example provided below at Figure 4 is an alternative screw terminal wiring guide,

providing a shared cabling run of suitable high capacity cable for the Vaisala device and heating

accessory (if required). The pin connections for the screw terminal connector and wire colours are

listed in Table 2 on

page 10

.

For installations that do require the optional heating accessory, ensure a high capacity cable

between the DC Power supply and the Vaisala device is used.

The screw terminal connector can be accessed from the bottom of the Vaisala device by unscrewing the three screws on

the Vaisala device's chassis, and carefully revealing the terminals. Cable runs can be fed through the small pluggable

holes in the base of the unit. Ensure to fully seal the Vaisala device once wiring is complete.

NOTE

Figure 4:  Wiring guide for Vaisala device screw terminal connector with split cabling for heating

The 16mm

2

Copper Cable to Earth Ground cable is a critical component for the correct operation of the surge protector.

Ensure this is installed correctly.

NOTE

IG04 Default Settings

IP Address

192.168.2.100 (Static)

Subnet Mask

255.255.255.0

HTTP Port

80

Innotech Port

20000

BACnet/IP

BACnet Port

47808

BACnet Instance

1509

Baud Rate

19200

Fault Timeout

30 seconds

Advertising