Function library

Function blocks

3.2.76

Angle integrator (PHINT1, PHINT2, PHINT3)

3−245

l

EDSVS9332K−EXT EN 4.0

C1150 = 0

C1150 = 1

The input PHINT3−LOAD is state−triggered (HIGH level).

·

PHINT3−LOAD = HIGH

– The integrator is loaded with the input value at PHINT3−SET.
– Sets the output PHINT3−STATUS = LOW

The input PHINT3−LOAD is edge−triggered (LOW−HIGH edge).

·

PHINT3−LOAD = LOW−HIGH edge

– The integrator is loaded with the input value at PHINT3−SET

and starts adding from this point

– Sets the output PHINT3−STATUS = LOW

P H I N T 3 - O U T

+ 3 2 7 6 7 r e v .

- 3 2 7 6 7 r e v .

+ C 1 1 5 1

- C 1 1 5 1

t

t

P H I N T 3 - S T A T U S

Fig. 3−200

Function of PHINT3 with constant input value when C1150 = 0 and C1150 = 1

l

The FB integrates speed or velocity values at PHINT3−IN to a angle (distance).

l

PHINT3−OUT outputs the counter content of the bipolar integrator.

– A positive value at PHINT3−IN increments the integrator (counter content is increased).

– A negative value at PHINT3−IN decrements the integrator (counter content is reduced).

l

If the counter content exceeds the value of +32767 encoder revolutions (

¢ +2147483647 inc)

– an overflow occurs. The counting is continued with the value −32768,

– PHINT3−STATUS switches to HIGH when the value (+) C1151 is reached

l

If the counter content falls below the value of −32768 encoder revolutions
(

¢ −2147483648 inc)

– an overflow occurs. The counting starts at the value +32767,

– PHINT3−STATUS switches to HIGH when the value (−) C1151 is reached