Function blocks

3.2.102

Welding bar control (WELD1)

3−329

l

EDSVS9332K−EXT EN 4.0

3.2.102.6

Weld1 mode: Distance with saving (C1446 = 2)

The value at the input WELD1−TIME is interpreted as a distance. WELD1−TIME is saved for the further
cycle when phase 2 of the profile is started (see basics of welding bar control).

Output of status information

l

WELD1−T−ERR = HIGH: The total length and the sum of times of the three sections
WELD1−LEN−C (close), WELD1−TIME (weld) and WELD1−LEN−O (open) do not agree. The
reasons may be as follows:

– Wrong profile selection

– Line speed too high

In this case the welding time is automatically reduced to avoid a disturbance of the motion sequence.

l

WELD1−DIR−ERR = HIGH: A negative master angle is assigned to the input WELD1−XIN.
Remedy:

– Invert master angle

– Invert direction of rotation of the welding bar drive at the function block CCTRL.

l

WELD1−ON = HIGH: Welding phase is active

0

WELD1−TIME is "frozen" when phase 2 is started by setting C1446 = 2 (distance with saving).

The distance WELD1−TIME" remains constant for the cycle.