Commissioning

Configuring the digital inputs and outputs

Digital inputs for communication via the MotionBus (CAN) X4

6

l

141

EDBCSXM064 EN 11.0

6.12.1

Digital inputs for communication via the MotionBus (CAN) X4

Setting C4011 = 0:

Terminal

Function

Level

Response

X6/DI1

Quick stop (QSP)

LOW

The drive is decelerated to standstill within the deceleration
time set in C0105.

HIGH

The motor follows the setpoint selection.

X6/DI2

Reference switch/
Touch probe sensor

LOW

No response

HIGH

Activation of reference switch/touch probe sensor (both edge
active)

X6/DI3

Positive hardware limit
switch

LOW

The controller reports the activation of the positive hardware
limit switch to the control. A further safety measure can be
implemented by wiring the emergency−off circuit.

HIGH

No response

X6/DI4

Negative hardware limit
switch

LOW

The controller reports the activation of the negative
hardware limit switch to the control. A further safety
measure can be implemented by wiring the emergency−off
circuit.

HIGH

No response

6.12.2

Digital inputs for communication via the automation interface (AIF) X1

Setting C4011 = 1:

Terminal

Function

Level

Response

X6/DI1

Sync source

LOW

No sync

HIGH

Sync is active

X6/DI2

Reference switch/
Touch probe sensor

LOW

No response

HIGH

Activation of reference switch/touch probe sensor (both edge
active)

X6/DI3

Positive hardware limit
switch

LOW

The controller reports the activation of the positive hardware
limit switch to the control. A further safety measure can be
implemented by wiring the emergency−off circuit.

HIGH

No response

X6/DI4

Negative hardware limit
switch

LOW

The controller reports the activation of the negative
hardware limit switch to the control. A further safety
measure can be implemented by wiring the emergency−off
circuit.

HIGH

No response