Setting the polarity of digital inputs and outputs, Commissioning – Lenze ECSCMxxx User Manual

Page 142

Advertising
background image

Commissioning

Configuring the digital inputs and outputs
Setting the polarity of digital inputs and outputs

6

l

142

EDBCSXM064 EN 11.0

6.12.3

Setting the polarity of digital inputs and outputs

The polarity can be set for each digital input and output. This determines whether the
input or output is HIGH active or LOW active.

The following are available:

ƒ

4 digital inputs (X6/DI1 ... DI4)

ƒ

1 digital output (X6/DO1)

ƒ

1 relay output (X25/BD1, BD2)

)

Note!

If the touch probe function or synchronisation via digital input X6/DI1 are
used, the set polarities are not taken into account.

The GDC contains codes for setting the polarity of digital inputs and outputs in the
parameter menu under Terminal I/O:

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0114

Polarity of the digital inputs
(DIGIN)

^ 142

1 DIGIN pol

0

{1}

HIGH level active)
{LOW level active}

X6/DI1

2 DIGIN pol

0

{0}

HIGH level active)
{HIGH level active}

X6/DI2

3 DIGIN pol

0

{1}

HIGH level active)
{LOW level active}

X6/DI3

4 DIGIN pol

0

{1}

HIGH level active)
{LOW level active}

X6/DI4

0

HIGH level active)

1

LOW level active

C0118

Polarity of the digital outputs

^ 142

1 DIGOUT pol

0

HIGH level active

X6/DO1 (DIGOUT_bOut1_b)

2 DIGOUT pol

0

HIGH level active

X25 (DIGOUT_bRelais_b, brake
connection)

0

HIGH level active

1

LOW level active