Controller enable (CINH = 0)

6

l

169

EDBCSXM064 EN 11.0

6.15

Controller enable (CINH = 0)

The controller will only be enabled internally if no signal sources relevant for the controller
inhibit (CINH) are activated (i.e. CINH−signal sources = 0).

The following table shows the conditions for controller enable:

Source of the
Controller inhibit

Controller
inhibit

Controller
enable

Note

Terminal X6/SI1

0 ... +4 V
(LOW level)

+13 ... +30 V
(HIGH level)

For controller enable, X6/SI1 must be
= HIGH and X6/SI2 must be = HIGH.

Terminal X6/SI2

0 ... +4 V
(LOW level)

+13 ... +30 V
(HIGH level)

C0040

C0040 = 0

C0040 = 1

Operating
module/keypad

s key

u key

Inhibiting with

s key is only possible if

the

s key is assigned with "CINH" via

C0469.

Fault

l

In case of TRIP

l

In case of
message

No fault active

For check see

^ 263.

Control word

l

MotionBus
(

^ 131)

C3153/Bit 9 = 1

C3153/Bit 9 = 0

GDC function key:

l

<F9> key (inhibit/stop controller)

Note: With ECS−M, the controller is enabled
via the master control!

l

C4040

C4040/Bit 9 = 1

C4040/Bit 9 = 0

Fieldbus module

See operating instructions for the respective fieldbus module.

LED status displays

LED

Operating state

Red

Green

Off

On

Enable through master control

l

X6/SI1 = HIGH

l

X6/SI2 = HIGH

Off

Blinking

No enable through master control

l

X6/SI1 = HIGH

l

X6/SI2 = HIGH

)

Note!

All signal sources act like a series connection of switches which are
independent of each other.